Err33 Elevator speed abnormal
101: The detected running speed during normal-speed running exceeds the limit.
102: The speed exceeds the limit during inspection or shaft auto-tuning.
103: The speed exceeds the limit in shorting stator braking mode.
104: The speed exceeds the limit during emergency running.
105: The emergency running time protection function is enabled (set in Bit8 of F6-45), and the running time exceeds 50s, causing the timeout fault.
How to fix Error 33 Nice3000 new.
101:
• Check whether the encoder is used properly.
• Check the setting of motor nameplate parameters.
Perform motor auto-tuning again.
102: Attempt to decrease the inspection speed or perform motor auto-tuning again.
103: Check whether the shorting PMSM stator function is enabled.
104, 105:
• Check whether the emergency power capacity meets the requirements.
• Check whether the emergency