Err 35 Shaft autotuning data abnormal
● Subcode 101: When shaft auto-tuning is started, the elevator is not at the bottom floor or the down slow-down switch is invalid,
● Subcode 102: The system is not in the inspection state (inspection switch not turned on) when shaft auto-tuning is performed.
● Subcode 103: It is judged upon power-on that shaft auto-tuning is not performed.
● Subcodes 104, 113, 114: In distance control mode, it is judged at running startup that shaft autotuning is not performed.
● Subcode 105: The elevator running direction and the pulse change are inconsistent.
● Subcodes 106, 107, 109: The plate pulse length sensed at up/down leveling is abnormal.
● Subcodes 108, 110: No leveling signal is received within 45s continuous running.
● Subcodes 111, 115: The stored floor height is smaller than 50 cm.
● Subcode 112: The floor when auto-tuning is completed is not the top floor.
Solution Error 35 Nice 3000 :
1. Handling at inspection-speed commissioning: Err35 (subcode 103) is reported at each power-on because shaft auto-tuning is not performed before inspection-speed commissioning. This fault does not affect inspection-speed commissioning and you can hide the fault directly on the operation panel.
2. Handling at normal-speed commissioning and running :
Subcode 101: Check that the down slow-down switch is valid, and that F4-01 (Current floor) is set to the bottom floor number.
Subcode 102: Check that the inspection switch is turned to inspection state. Subcodes 103, 104, 113, 114: Perform shat auto-tuning again.
Subcode 105: Check whether the elevator running direction is consistent with the pulse change in F4-03: F4-03 increases in up direction and
decreases in down direction. If not, change the value of F2-10 to ensure consistency.
Subcode 106, 107, 109:
● Check that NO/NC state of the leveling sensor is set correctly.
● Check whether the leveling plates are inserted properly and whether there is strong power interference if the leveling sensor signal blinks.
● Check whether the leveling plate is too long for the asynchronous motor.
Subcodes 108, 110:
● Check whether wiring of the leveling sensor is correct.
● Check whether the floor distance is too large, causing running time-out. Increase the speed set in F3-11 and perform shaft auto-tuning again to ensure that learning the floors can be completed within 45s.
Subcodes 111, 115:
Enable the super short floor function if the floor distance is less than 50 cm. If the floor distance is normal, check installation of the leveling plate for this floor and check the sensor.
Subcode 112:
Check whether the setting of F6-00 (Top floor of the elevator) is smaller than the actual condition.
Err 35 occurred before the run contactor pick-up
1 .check whether the 1st down forced deceleration is valid
2 .F4-01=1
3 .whether the inspection switch on the inspection state and able to done the inspection run
4 .F0-00=1
Err 35 occurred as soon as the run contactor pick-up
1 .check whether the inspection switch on the inspection state
Err 35 occurred during running
1 .check whether running overtime, run over the time of Err 35 occurred when meet the 1st levelling position
1 .Whether the F4-03 INCREASE WHEN UP, DECREASE WHEN DOEN, switch the main board PGA and PGB if it is not .
2 .Level sensor N .O, N .C .setting error .
3 .level sensor signal flash, check the plate
Err 35 during running:
1 .check whether run overtime of F9-02 setting value, and no receiving of levelling signal
2 .the floor distance less than 50cm, check the sensor
3 .the F6-00 setting too small Run to the top floor:
1 .the 1st forced slowdown is valid and juadge on the door-area, check whether the learned floor amount are same as the setting of F6-00 and F6-01 .
2 .Error occurs if the lifting height less than 50cm Err35 occures when power-on Check whether the plate length is 0 after power-on